Post Offer Free
China Relay Test Set Online Market Group  

Gold Index: 4944

You are here: home  > High Voltage Protection Relay Testing

High Voltage Protection Relay Testing 

Place of Origin: Zhejiang, China (Mainland) 
inquire
Add to My Favorites
HiSupplier Escrow
Share |

Product Detail

Model No.: K3063i


 
High Voltage Protection Relay Testing
 
<sp

 

High Voltage Protection Relay Testing

 

Relay protection test devices
1.Easy test
2.operation menu, Simple operation
3.Nominal input voltage:220VAC
4.Power:1000VA

 

 

1. Unique self-protection system assure the powerful protection when instrument is operating, automatic stop the output when the network is abnormal ;
2. Unique power switch and amplifier technology, so the output precision and power efficiency and factor are increased, which conforms to international tendency of energy save and environmental protection;
3. With alarm function of housing grounding testing and external voltage input, to guaranty personal security;
4. Two in one of meter and source, with function of both internal and external testing, self-calibration, oscillograph, and the duration of each oscillograph reaches 50S (optional function);
5. Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A (Poleless and adjustable);
6. Function of transducer and energy meter testing (optional function);
7. Testing interface offer unique output monitoring function and Pre-curve-tracing function, helps more on the spot analysis;
 

 

Technical Data of K3063i 

Voltage generators

Setting 

Range

4-phase AC (L-N)

4 x 0 ... 300 V 

2-phase AC (L-L)

2 x 0 ... 600 V

Power

4-phase AC (L-N)

4 x 110VA,  at 0 ... 300 V

2-phase AC (L-L)

2 x 220VA,  at 0 ... 600 V

Accuracy

<0.07% reading + 0.03% range guaranteed 

at 0 ... 300 V

<0.02% reading + 0.01% range typical 

at 0-300V

Resolution

1mV

Current generators

Setting 

Range

6-phase AC (L-N)

6 x 0 ... 30 A

3-phase AC (L-N)

3 x 0 ... 60 A (Group A II B)

1-phase AC (3L-N)

1 x 0 ... 180 A 

Power

6-phase AC (L-N)

6x 450VA , at 0 ... 30A 

3-phase AC (L-N)

3x 520VA,  at 0 ... 60A (Group A II B) 

1-phase AC (3L-N)

1 x 1000 VA,  at 0 ... 180A (Max.)

Accuracy

<0.07% reading + 0.06% range guaranteed at 0-30A 

<0.02% reading + 0.02% range typical at 0-30A

Resolution

1mA

Generators,  general

bigPhoto
 Mr. Willi

Tel: 86-25-88681234
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

China Relay Test Set Online Market Group [China (Mainland)]


Business Type:Manufacturer
City: Nanjing
Province/State: Jiangsu
Country/Region: China (Mainland)

You May Like:

Product (103)